What OPC Servers will work with the ANC-100e gateway running the DH+ firmware?

There are several OPC servers that have been tested or are known to work through ANC-100e running the DH+ bridge firmware: RSLinx Classic using the Ethernet Devices driverWonderware using the DASABCIP driverKepware using the ControlLogix Ethernet driver TopServer using AB controLogix Ethernet Driver PeakHMI AB PCCC SLC Master Driver Additional OPC Servers may work with […]

What are common things that prevent reliable DH+ communications on the ANC-100e gateway running the DH+ Bridge FW?

If the NS or NET LED is not solid green then check the recommendations below:

1) For networks running at 57k6 or 115k2 bauds it is necessary to have 150 ohm resistors on each end of the network (for 230k4 use 82 ohm resistors)
2) Ensure that at least 10′ or 3 meters of cable is used between gateway and any surrounding nodes
3) Ensure that the outer braided shield has been grounded in one place to reduce noise

How many Data Highway Plus Nodes can a single ANC-100e communicate with?

The ANC-100e’s Data Highway Plus firmware does not have a specific limit on the number of nodes it can communicate with (beyond the inherent limits of the DH+ protocol itself), however, be aware that DH+ is a serial based token passing protocol, and thus there will be significant delays in update rates for each additional node on the network that may hold the token.