Note: Before proceeding, make sure
- ANC-120e Driver is installed (Only if using ANC-120e)
- Network Adapter is correctly configured to access ANC-120e or ANC-100e ANC-120e is connected to the computer and DH+ network or
- ANC-100e is connected to the same Ethernet network or directly to your computer, and to the DH+ network.
For our example:
ANC-100e or ANC-120e IP address = 192.168.0.230
SLC5/05 IP address = 192.168.0.231
SLC5/04 DH+ node = 03
1. Go to “Comms” Menu and select “Who Active Go Online” Option
2. Select the SLC5/05 that you want to program and click the OK Button
![](https://automation-networks.com/wp-content/uploads/2024/04/SLC-505-manual-1.jpeg)
3. Insert a MSG instruction and configure it as required. For our example, we will use a MSG instruction with the following options:
Read/Write: Read
Target Device: 500CPU
Local/Remote: Remote
Control Block: N7:10
4. Once done with the above, click on “Setup Screen” to continue the MSG instruction configuration.
![](https://automation-networks.com/wp-content/uploads/2024/04/SLC-505-manual-2.jpeg)
5. We want to read F8:0 address from the SLC5/04 on DH+ into F8:0 address of our SLC5/05.
6. Select Channel 1 for Ethernet Communication
7. Select “MultiHop” Yes to enable the MultiHop Tab
![](https://automation-networks.com/wp-content/uploads/2024/04/SLC-505-manual-3.jpeg)
8. On the MultiHop tab enter the following, using the “insert key” on your keyboard to add each “Hop”:
This SLC5/05: Channel 1 to EtherNet/IP 192.168.0.230
Logix Backplane to Backplane Slot 1
1756-DHRIO Channel A to Remote Link ID 0
Remote DH+ to Remote Station 3
Note: Depending on your settings, the IP address of your ANC-100e or ANC120e, and the remote station on DH+ may change. The backplane slot, the remote link ID and 1756-DHRIO Channel will always be the same.
Once information has been entered just close the window.
![](https://automation-networks.com/wp-content/uploads/2024/04/SLC-505-manual-4.jpeg)
9. Save and download the program to your SLC5/05, and now it should read/write successfully to your SLC5/04 on DH+
![](https://automation-networks.com/wp-content/uploads/2024/04/SLC-505-manual-5.jpeg)